S13-M.ZT Series Intelligent On-Load Tap-Changing Transformer
+
  • S13-M.ZT Series Intelligent On-Load Tap-Changing Transformer

S13-M.ZT Series Intelligent On-Load Tap-Changing Transformer

The intelligent on‑load tap‑changing and capacity‑adjusting transformer features two capacity settings—high and low—and can automatically switch between them in response to load variations, all without interrupting power. When the load is light or near no‑load conditions, the transformer transitions from high to low capacity, significantly reducing no‑load losses while eliminating the inconvenience of manual, outage‑required capacity adjustments. This approach truly achieves energy savings and intelligent operation.




Product Details


The intelligent on‑load tap‑changing, capacity‑adjusting transformer features two distinct capacity settings and can automatically switch between them without interrupting power supply in response to load variations. When the load is light or near no‑load conditions, the transformer reduces its capacity from the higher setting to the lower one, significantly cutting no‑load losses while eliminating the inconvenience of manual, outage‑required operations associated with off‑load capacity adjustment. This design truly achieves energy savings and intelligent operation. The product is particularly well suited for rural distribution networks with large seasonal load fluctuations, residential neighborhoods experiencing pronounced day‑night load variations, street‑light substations, urban commercial districts, part‑time industrial zones, and pump‑set transformers in oilfields. It is also ideal for 35 kV power transformers subject to substantial load changes. Our company’s intelligent on‑load tap‑changing, capacity‑adjusting transformer is protected by multiple patents and comprises a transformer, an on‑load tap‑changing switch, and a control cabinet housing the on‑load tap‑changing controller. Its capabilities—including data storage, remote signaling, remote control, remote adjustment, remote measurement, intelligent networking, reactive power compensation control, and anti‑theft protection—far surpass those of conventional laminated‑core and amorphous‑material transformers and other energy‑saving products.

 

Patterns and Meaning

Performance Parameters

Table: Technical Parameters of the 10 kV S13-M.ZT Series Intelligent On-Load Tap-Changing Transformer:

Model number

Rated voltage Combination (kV)

Connection Group

No-load loss (W)

Load loss (W)

Short-circuit impedance (%)

No-load Current (%)

S13-M-ZT-160(50)

10/0.4>

Dyn11
/

Yyn0

200 (100)

2310 (870)

4.0

0.8 (1.6)

S13-M-ZT-200(63)

240 (110)

2730 (1040)

4.0

0.7 (1.5)

S13-M-ZT-250(80)

290 (130)

3200 (1250)

4.0

0.7 (1.4)

S13-M-ZT-315(100)

340 (150)

3830 (1500)

4.0

0.7 (1.4)

S13-M-ZT-400(125)

410 (170)

4520 (1800)

4.0

0.6 (1.3)

S13-M-ZT-500(160)

480 (200)

5410(2200)

4.0

0.6 (1.2)

S13-M-ZT-630(200)

630 (200)

6200 (2600)

4.5

0.5(1.1)

 

Energy Efficiency Analysis

Annual Operating Costs and Payback Period:

Cy = [8600 × (P0 + 0.05 × lo × SN / 100) + 2200 × (Pk + 0.05 × UK × SN / 100)] × 0.5 In the above formula:

Cy denotes the annual operating cost of the transformer, in yuan;

PO denotes no-load loss, with the unit being kilowatts;

Pk is the load loss, with the unit being kilowatts;

SN denotes the rated capacity, with the unit being kVA;

Uk is the percentage of the short-circuit impedance, %;

Io is the no-load current, expressed as a percentage, %;
0.5 represents the electricity price, in yuan per kilowatt-hour; 8600 and 2200 They are, respectively, the equivalent full-load operating hours. Q_load denotes the equivalent full-load operating hours, with a load factor of 0.5.

Based on the aforementioned data and relevant performance indicators, the annual operating costs of the S13-M-ZT series intelligent on‑load tap‑changing, capacity‑adjustable distribution transformers were calculated and compared with those of the S11 series conventional three‑phase oil‑immersed distribution transformers. It is assumed that the on‑load tap‑changing, capacity‑adjustable transformer operates in high‑capacity mode for 3 months and in low‑capacity mode for 9 months per year. Calculations were performed using the corresponding technical parameters of the distribution transformers; specific data are provided in Table 3.

On‑load tap‑changing and capacity‑adjustable transformers align with the power‑distribution sector’s evolving trends toward energy efficiency, intelligent operation, high efficiency, and stable power quality. By automatically tracking load variations, they adjust the rated output capacity of the terminal distribution transformer as needed, ensuring timely and appropriate power supply. This approach significantly reduces no‑load losses by approximately 40% to 50%, improves the grid’s power factor, lowers reactive power in the distribution network, decreases network losses, and reduces the required capacity of power‑factor correction capacitors, thereby opening a new avenue for the development of energy‑efficient distribution networks and delivering substantial economic benefits to society.

Table 2: Comparison of Annual Operating Costs Between S13-M-ZT Series Intelligent Capacity-Regulating Distribution Transformers and S11-Type Distribution Transformers

Capacity
(kVA)

Annual operating cost of on-load tap-changing transformer (RMB)

Annual operating cost of a standard distribution transformer (RMB)

Annual Operating Cost Savings (RMB)

Annual operation Cost Reduction (%)

160 (50)

2289

4647

2358

51

200 (63)

2710

5550

2840

51

250 (80)

3227

6543

3316

51

315 (100)

3816

7918

4102

52

400 (125)

4588

9531

4943

52

500 (160)

5497

11265

5768

51

630 (200)

6608

13352

6744

51

 

Appearance diagram and installation dimensions

Outline Drawing of a 10 kV Intelligent On-Load Tap-Changing Distribution Transformer

Table 3: S11-M-ZT Series Intelligent Capacity-Regulating Transformer  
External Mounting Dimensions and Weight Table

Capacity
(kVA)

External dimensions (mm)

Installation
Dimensions (mm)

Weight (kg)

Length L

Width B

Height H

L2

B2

160 (50)

1380

990

1230

820

820

1100

200 (63)

1400

1070

1230

820

820

1220

250 (80)

1440

1120

1250

820

820

1370

315 (100)

1480

1170

1350

820

820

1620

400 (125)

1620

1190

1330

820

820

1910

500 (160)

1710

1240

1350

820

820

2200

630 (200)

1850

1270

1450

820

820

2660

Tags:

S13-M.ZT Series Intelligent On-Load Tap-Changing Transformer

Product Inquiry

If you are interested in our services, please fill out the form below and we will contact you as soon as possible.