110 kV-class intelligent three-phase on-load tap-changing power transformer
+
  • 110 kV-class intelligent three-phase on-load tap-changing power transformer

110 kV-class intelligent three-phase on-load tap-changing power transformer

The 110 kV three-phase oil-immersed on-load tap-changing power transformer incorporates a series of major innovations in materials, manufacturing processes, and structural design. It features a compact footprint, light weight, high efficiency, low losses, reduced noise, and reliable operation, thereby significantly cutting grid losses and operating costs and delivering substantial economic benefits. It is suitable for use in power plants, substations, and large industrial and mining enterprises.




Product Details


The 110 kV three-phase oil-immersed on-load tap-changing power transformer incorporates a series of major innovations in materials, manufacturing processes, and structural design. It features a compact footprint, light weight, high efficiency, low losses, reduced noise, and reliable operation, thereby significantly cutting grid losses and operating costs and delivering substantial economic benefits. It is suitable for use in power plants, substations, and large industrial and mining enterprises.

This product complies with the following national standards: GB 1094.1-2013 “Power Transformers — Part 1: General Requirements,” GB 1094.2-2013 “Power Transformers — Part 2: Temperature Rise,” GB 1094.3-2003 “Power Transformers — Part 3: Insulation Levels, Insulation Tests, and External Insulation Air Gaps,” GB 1094.5-2003 “Power Transformers — Part 5: Short‑Circuit Withstand Capability,” and GB/T 6451-2015 “Three‑Phase Oil‑Immersed Power Transformers — Technical Parameters and Requirements.”

 

Operating environmental conditions

  1. Device Type: Outdoor
  2. Ambient temperature: maximum +40°C, minimum -30°C
  3. Altitude: ≤1000 m (for altitudes >1000 m, temperature rise must be corrected)
  4. Relative humidity: ≤90% (25°C)
  5. Installation location: Areas free of corrosive gases and significant dirt.

 

Technical Specifications

3-phase, double-winding, no-excitation voltage-regulating power transformer, rated capacity 6,300 kVA to 180,000 kVA

Rated capacity

(kVA)

Voltage combinations and tap ranges

Connection Group

No-load loss

kW (9)

Load loss

kW (9)

No-load current

%

Short-circuit impedance

%

High voltage kV

Low-voltage kV

6300

110±2×2.5%

115±2×2.5%

121±2×2.5%

6.3

6.6

10.5

YNd11

7.4

35.0

0.62

10.5

8000

8.9

42.0

0.62

10000

10.5

50.0

0.58

125000

12.4

59.0

0.58

160000

15.0

73.0

0.54

20000

17.6

88.0

0.54

25000

20.8

104

0.50

31500

24.6

123

0.48

40000

29.4

148

0.45

50000

35.2

175

0.42

63000

41.6

208

0.38

75000

13.8

15.75

18

21

47.2

236

0.33

12~14

90000

54.4

272

0.30

120000

67.8

337

0.27

150000

80.1

399

0.24

180000

90.0

457

0.20

Note 1: The -5% tap position corresponds to the maximum current tap.

Note 2: For transformers with a voltage rating lower than that of the step-up transformer, a tapless design is recommended. If operational requirements dictate, tap changers may be provided.

Note 3: When the transformer’s annual average load factor is between 45% and 46%, using the loss values listed in the table will yield the highest operating efficiency.

  1. Upon customer request, products with capacities beyond those listed in the table can be manufactured, with performance parameters tailored to specific requirements.
  2. Depending on the operating environment, we can offer specially designed products.
  3. For medium voltage, a voltage value different from those listed in the table may be selected, or a tap can be set; for high voltage, asymmetric regulating taps are chosen.
  4. The short-circuit impedance may be selected to differ from the values listed in the table.
  5. The final dimensions shall be subject to confirmation on the drawings following contract signing.

 

Structural features

110 kV-class three-phase, double-winding, on-load tap-changing power transformers can be customized to meet specific customer requirements, with various specifications available.

 

Tags:

110 kV-class intelligent three-phase on-load tap-changing power transformer

Product Inquiry

If you are interested in our services, please fill out the form below and we will contact you as soon as possible.