Wind‑Power‑Specific Combined Transformer Substation (American‑Style)
+
  • Wind‑Power‑Specific Combined Transformer Substation (American‑Style)

Wind‑Power‑Specific Combined Transformer Substation (American‑Style)




Product Details


A wind‑power‑specific pre‑assembled packaged substation is a complete substation in which the step‑up station required for wind power generation is manufactured and assembled at the factory. It includes a step‑up transformer, high‑voltage load switches, low‑voltage switchgear, and auxiliary equipment such as distribution transformers, all housed within a common enclosure and subjected to type testing. Its structural configuration is identical to that of European‑style packaged substations, which is why it is also referred to as a “wind‑power packaged substation.” Its performance fully complies with GB 17467‑2010, “High‑Voltage and Low‑Voltage Pre‑Assembled Substations.” Designed to meet the specific requirements of wind power generation, this new type of step‑up substation offers significant advantages, including high degree of integration, ease of installation, short construction timelines, low operating costs, robust structural strength, and excellent corrosion resistance. Consequently, it is ideally suited for harsh environmental conditions such as coastal areas, grasslands, and deserts. The product has successfully passed type tests conducted by the Wuhan High‑Voltage Research Institute, with performance fully meeting the operational requirements of wind farms.

 

Product Implementation Standard

GB 1094-2013 “Power Transformers”

GB/T 6451-2015 “Technical Parameters and Requirements for Three-Phase Oil-Immersed Power Transformers”

Reference implementation: JB/T 10217-2013 “Combined Transformer”

 

Operating environment

Altitude

≤4000 meters

Ambient temperature

Maximum temperature: +42°C, minimum temperature: -40°C

Humidity

Daily average relative humidity ≤ 95%; monthly average relative humidity ≤ 90%

Wind speed

Outdoor wind speed ≤ 45 m/s

Earthquake-resistant

Horizontal acceleration ≤ 0.4 m/s², vertical acceleration ≤ 0.15 m/s²

Installation site inclination

≤3°

Installation Environment

The surrounding air is free from significant contamination by corrosive or flammable gases, and the installation site is free from severe vibrations.

 

Product Structural Features

  • The fully insulated, compartmentalized combined transformer employs fully insulated cable prefabricated terminations on the 12 kV/40.5 kV sides, along with touch‑safe plug‑in surge arresters. The entire product features no exposed high‑voltage live parts, offering a high degree of protection and ensuring reliable safety.
  • Fully insulated, compartmentalized combined transformer: the transformer and the high-voltage components are housed in two separate enclosures, thereby addressing oil contamination of the transformer while enabling independent maintenance of the high-voltage components and the transformer.
  • 12 kV products are protected by insert-type fuses combined with backup protective fuses, while 40.5 kV products are protected by insert-type full-range protective fuses.
  • No leakage: each tank has undergone a sealing test at 50 kPa for 12 hours to ensure tightness and prevent leaks.
  • For high-voltage applications, a common‑box type combined transformer with dry‑type bushings for the high-voltage side offers convenient wiring, allows for a greater number of incoming and outgoing circuits, and features lower costs.
  • The equipment enclosure is coated using a rigorous painting process and finished with a UV‑resistant topcoat, ensuring excellent outdoor weather resistance.
  • The transformer has no separate enclosure, resulting in excellent heat dissipation.

 

 

Schematic Diagram of Product Structure and Appearance

 

Typical Scheme Diagram

Component Selection Table

Capacity

High-voltage switch

High-voltage fuse

High-voltage surge arrester

Low-voltage switch

Auxiliary transformer

40.5

40.5

40.5

600

BYF1-40.5

LS2B338H3

XRNT-40.5/25

HY5WZ-51/134

TBP-B-42

HKDW1 circuit breaker

KFW2 circuit breaker

SG-63/0.69

SF-3/0.69

The capacity can be determined based on the fan type.

660

XRNT-40.5/25

750

XRNT-40.5/25

900

XRNT-40.5/25

1400

XRNT-40.5/40

1600

XRNT-40.5/50

2200

XRNT-40.5/63

2350

XRNT-40.5/63

2800

XRNT-40.5/80

3300

XRNT-40.5/80