S13-M · RlD Three-phase three-dimensional wound-core distribution transformer
+
  • S13-M · RlD Three-phase three-dimensional wound-core distribution transformer

S13-M · RlD Three-phase three-dimensional wound-core distribution transformer

The S13 series wound‑core distribution transformers feature low losses, with load losses comparable to those of the latest‑generation S11 laminated‑core distribution transformers. According to GB/T 6415‑2008, their no‑load losses are reduced by an average of 20%, while also requiring less material and weighing less.




Product Details


The S13 series distribution transformers feature a wound‑core design, delivering low losses; their load losses are comparable to those of the newer S11 laminated‑core distribution transformers. In accordance with GB/T 6415‑2008, no‑load losses are reduced by approximately 20% on average. This series uses fewer materials, weighs less, and exhibits lower no‑load current. Magnetic flux is precisely aligned along the grain orientation of the cold‑rolled silicon steel sheets, significantly reducing noise levels—typically 3 to 5 dB below the limits specified in JB/T 10088‑2004. Furthermore, this transformer series offers robust short‑circuit withstand capability and high reliability. The clamping yokes primarily serve to secure the windings, and their insulation is integrated with trapezoidal spacers, ensuring uniform stress distribution across the entire core assembly. The core is fabricated from 30Q120 cold‑rolled silicon steel, with both the inner and outer frames of the three‑phase limbs adopting a coil‑type structure, while the core limbs feature a multi‑step stepped cylindrical cross‑section. After winding is completed, the core undergoes vacuum annealing. The tension bolts on the upper and lower clamping yokes are designed as integral units. Finally, the core surface is coated with epoxy resin to prevent deformation and corrosion.

Windings and Core: The low-voltage winding adopts a cylindrical configuration, with 1 to 6 conductors arranged in four layers (or double layers), using paper‑wrapped flat copper wire. The high-voltage winding is a multi‑layer cylindrical design, employing high‑strength aldehyde‑cured enamel‑coated round copper wire to ensure uniform electric field distribution. The windings are directly wound on a rotating form composed of toothed laminations and soft paper sleeves adhered to the core limbs. The yoke insulation is integrated with trapezoidal shims, achieving uniform stress distribution and securely clamping the core. A novel suspension‑plate positioning system enables precise longitudinal and transverse centering, ensuring stable core support and preventing any displacement.

Fuel tank: primarily of the corrugated type. Fuel tank ; Rectangular plate‑type radiator‑style fuel tanks are also available.

 

Patterns and Meaning

Main Technical Parameters

Technical specifications of the S13-type new energy-saving three-dimensional wound-core oil-immersed transformer.

Rated Capacity (kVA)

Voltage combination

No-load loss (W)

Load loss (W)

No-load current (%)

Short circuit
Impedance
(%)

Weight (kg)

Track gauge A×B (mm)

External dimensions (mm): Length × Width × Height

High-pressure regulation range

High-voltage tap range

Low pressure
(kV)

Connection Group

Main body
Weight

Insulating oil weight

Total weight

30

11;
10.5;
10;
6.6;
6.3;
6;

±2×2.5
Or
±5%;

0.4

Dyn11;
Yyn0;

Yzn11

80

630/ 600

0.30

 

178

113

377

380x550

1028x682x1199

50

100

910/ 870

0.24

4.0

236

111

435

380x550

1025x683x1224

80

130

1310/ 1250

0.22

313

146

553

380x550

1096x722x1314

100

150

1580/ 1500

0.21

356

148

607

380x550

1096x722x1334

160

200

2310/ 2200

0.19

484

185

797

400x660

1080x935x1441

200

240

2730/ 2600

0.18

556

228

937

400x660

1109x960x1444

250

290

3200/ 3050

0.17

655

263

1091

400x660

1196x1036x1457

315

340

3830/ 3650

0.16

769

274

1269

550x820

1276x1105x1467

400

410

4520/ 4300

0.16

4.5

896

323

1437

550x820

1306x1131x1542

500

480

5140/ 5100

0.16

1044

433

1872

550x820

1483x1284x1592

630

570

6200

0.15

1352

414

2085

550x820

1395x1210x1649

800

700

7500

0.15

1613

496

2481

550x820

1526x1321x1711

1000

830

10300

0.14

1703

656

3000

550x1070

1717x1487x1726

1250

970

12000

0.13

2065

702

3449

550x1070

1711x1482x1829

1600

1170

14500

0.12

2592

1045

4450

550x1070

1880x1628x1938

 

Tags:

S13-M · RlD Three-phase three-dimensional wound-core distribution transformer

Product Inquiry

If you are interested in our services, please fill out the form below and we will contact you as soon as possible.